Leakage indication lamps should be compulsorily connected.
· Every DC takes off should be through fuses (H.R.C.) or MCB.
· Leakage in DC should be attended on top priority.
· Check electrolyte level in cell every morning. If low, top up with distilled water.
· Check up the voltage & specific gravity of six cells in each shift and record.
· Ensure battery in floating condition normally.
· Never charge at a voltage higher than 2.4 V/Cell.
· If any cell found with low volt/sp. Gravity, bypass & charge separately and then replace.
· Once in a day AC to charger should be made off, and measure DC
· Ensure closing & tripping of CB (not in service) in AC off condition.
· Restore AC immediately after testing.