Different protections applied for capacitor bank are as below:-
External fuses (for 11KV) and Internal fuses (for 22/66/132 KV capacitor banks) of adequate thermal capacity to take care of internal faults.
IDMT over current & earth fault relay for over current and earth fault protection.
Over voltage, instantaneous no voltage protection & power factor control.
Neutral Current Transformer (NCT) for current unbalance detection in case of 22/66/132 KV double star capacitor banks.
Residual Voltage Transformer (RVT) for unbalance voltage detection of 11KV single star bank as well as for quick discharge.
Series reactors to limit parallel switching current and to reduce the effect of harmonics.
Off load isolators/ load break switches to isolate capacitor banks.
Capacitor switches for switching pole mounted capacitor banks.
Discharge resistors to reduce residual voltage from crest value of rated voltage to 50 volts or less within 5 minutes.
Definitions CSD (Controlled Switching Device): A device that is installed at the relay and control panel to overcome the transient behaviour of voltage and current during switching. This device synchronizes the switching of each pole of the circuit breaker according to the zero crossing of the corresponding phase. This device is also known as a phase synchronizing device, or PSD for short. Requirement When we switch off an online circuit breaker to disconnect an inductive load, we ideally want to interrupt the current of the system at the zero crossing of the current waveform. However, this is practically impossible to achieve. In a normal circuit breaker, the current interruption may occur near the zero crossing point, but not exactly at it. Since the load is inductive, this sudden interruption of current causes a high rate of change of current (di/dt), which results in a high transient voltage in the system. In low or medium voltage power systems, this transient voltage during circui...